ISOLATED TRANSMITTER • DC V-A > U/I
The OMX 333 model series are simple DIN rail mountable programmable transmitters.
Type OMX 333DC is a transmitter used for measurements of higher DC voltage and current easily adjustable in the instrument´s menu.
The instrument is based on a single-chip microcontroller with a 16-bit A/D and D/A converter, which ensures good accuracy, stability and easy operation of the instrument.
-
input: ±0,5/±1/±5 A; ±25/±50/±100/±200/±400 V
-
output: 0…5/20 mA/4…20 mA
0…2/5/10 V/±10 V -
digital filters, tare, linearization
-
galvanic isolation: 2,5 kVAC
-
width 25 mm
-
DIN rail mounting
-
power supply 10…30 VDC/24 VAC
TECHNICAL DATA:
InputDCRangemenu selectable
0…0,5 A< 15 mVInput 50…1 A< 30 mVInput 50…5 A< 150 mVInput 5±25 V10 MOhmInput 1±25 V10 MOhmInput 1±100 V10 MOhmInput 1±200 V10 MOhmInput 1±400 V10 MOhmInput 1External inputsNumber1 input, on contactFunctionsOFF No function HOLD Stopping measurement (option: Display - Analog output - Limits) TARA Tare activation ProjectionSignalizing LEDL1, L2 Limits L1, L2 (red) Lo, Hi Signalization, settings and errors (red/green) SettingsControlThe instrument is controlled and set by two buttons and a DIP switch on the front panelOM LinkCompany communication interface for operation, setting and update of device firmware
OM Link program is also designed for visualization and filing of meas. values from more instrumentsInstrument accuracy and functionalityTemperature coefficient50 ppm/°CAccuracy±0,15 % of range (for 20 measur./s)Rate0,5…80 measur./sOverload capacity2x; 10x (t < 30 ms) - not for > 200 V and 5 ALinearizationlinear interpolation in 25 points (only via OM Link)Digital filtersexponential mean from 2…100 measurements rounding setting projection step for display FunctionsTare designed to reset display on non-zero input signal Watch-dogreset after 500 msCalibrationat 25°C and 40 % r.h.ComparatorsTypeDigital, menu adjustable, contact connect. < 50 msModeHysteresis switch. point, hysteresis band ''Mez ± 1/2 Hys.'' and time (0 ... 99.9 s) determ. switching delay Ready output switching signals perfect status Error output switching signals error status Output1x relay, switch-over contact (250 VAC/30 VDC, 3 A)
2x relay, switch-over contact (250 VAC/30 VDC, 3 A)
2x open collector (30 VDC/100 mA)
4x open collector (30 VDC/100 mA)Data outputsProtocolASCIIData format8 bits + no parity + 1 stop bit (ASCII)Rate600…230 400 BaudRS 485isolated, addressing max. 31 instrumentsAnalogue outputsTypeIsolated, programmable with a 16-bit D / A converter, type and range are menu selectableTemperature coefficient15 ppm/°CNonlinearity±0,1 % of rangeRateresponse to value change < 1 msRanges0...2 V, 0...5 V, 0...10 V, ±10 V, 0...5 mA, 0...20 mA, 4...20 mACompensation600 Ohm/12 VError stateat range of 4...20mA
error message indication (<3.0 mA)
Detection of current loop interruptionPower supplyPower supply10…30 VDC/24 VAC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolatedCurrent draw< 2 W/2 VAOperating conditionsConnectionconnector terminal board, cable section < 1,5 mm2Stabilization periodwithin 15 minutes after switch onOperating temperature-20°…60°CStorage temperature-20°…80°CProtection classIP20El. safetyEN 61010-1, A2Dielectric strength2,5 kVAC within 1 min. between pow. supply, input and output
2,5 kVAC within 1 min.between input and data/anal. outputInsulation resistancefor polution degree II, measuring cat. III.
power supply 550 V (ZI), 255 V (Di)* EMCEN 61326-1Mechanical propertiesMaterialPA 66, non-inflammable UL 94 V-I (blue)Dimensions25 x 79 x 110 mm (w x h x d)InstallationDIN rail, width 35 mm